IEVref:442-09-09ID: 442-09-09
Language:enStatus: Standard
Term: critical relative humidity
Synonym1:
Synonym2:
Synonym3:
Symbol:
Definition: value of the relative humidity when the impulse withstand voltage of a creepage distance has dropped to 95 % of the value that was measured at 70 % relative humidity


Publication date:2014-11
SourceIEC 60664-5:2007, 3.2
Replaces:
Internal notes:
CO remarks:
TC/SC remarks:
VT remarks:
Domain1:Electrical accessories
Domain2:Insulation coordination for low voltage equipment
Domain3:
Domain4:
Domain5: